Date Inspected | Location in School | Health & Safety Issue Observed | Class | Action Taken By | Date Action Taken | Details |
10/02/23 | 124 | ventilation (specify) | A | Caretaker | 10/03/23 | Details |
10/02/23 | Gym A&B | door/access door (specify) | A | Caretaker | 10/03/23 | Details |
10/02/23 | Drama Room | furniture unsafe - requires repair | A | Caretaker | 10/03/23 | Details |
10/02/23 | Weight Room (lower room across from Auditorium) | combustible material being displayed that is not fire rated/treated | A | | | Details |
11/22/23 | 104 | window covering recommended on 1st floor (emergency lockdown procedures) | B | | | Details |
11/22/23 | 106T | door/access door (specify) | A | Caretaker | 11/27/23 | Details |
11/22/23 | 111 | extension cord/power bar - inappropriate use of extension cord/power bar (be specific) | B | | | Details |
12/19/23 | Hallway | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/04/24 | Details |
12/19/23 | 133 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 01/04/24 | Details |
12/19/23 | Exit 5 | door/access door (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 115 | window covering recommended on 1st floor (emergency lockdown procedures) | B | Caretaker | 01/04/24 | Details |
12/19/23 | Office - Music | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/04/24 | Details |
12/19/23 | Office - Music | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 01/04/24 | Details |
12/19/23 | 113 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 119 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 120 | ceiling tiles missing/loose | A | Caretaker | 01/04/24 | Details |
12/19/23 | 133 | ceiling tiles missing/loose | A | Caretaker | 01/04/24 | Details |
12/19/23 | 129 | ceiling tiles missing/loose | A | Caretaker | 01/04/24 | Details |
12/19/23 | 113 | ceiling damaged (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 116 | ceiling damaged (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | Hallway | ceiling damaged (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | Hallway | ceiling damaged (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 114 | temperature does not meet TDSB Guideline | A | Caretaker | 01/04/24 | Details |
12/19/23 | Exit 5 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 114 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 114 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 123 | ceiling tiles missing/loose | A | Caretaker | 01/04/24 | Details |
12/19/23 | 126 | door/access door (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 126 | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 01/04/24 | Details |
12/19/23 | 106T | door/access door (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | Hallway | door/access door (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | 126 | drain (specify) | A | Caretaker | 01/04/24 | Details |
12/19/23 | Staff Washroom | paint flaking, chipping, possible lead exposure | A | Caretaker | 01/04/24 | Details |
12/19/23 | 112 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 01/04/24 | Details |
01/10/24 | 106T | door/access door (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 123 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 131 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 115 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 117 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 208 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 210 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 210T | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 213 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 213 | door/access door (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 217 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 151 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 151 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 114 | air - return/supply (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 126 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 124 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 124 | window damaged, in need of repair (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 208 | window covering damaged/in need of repair | A | Caretaker | 01/18/24 | Details |
01/10/24 | 208 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 213 | ceiling damaged (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 217P | door/access door (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 114 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 112 | lighting in need of repair (maintenance issue) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 115 | window covering recommended on 1st floor (emergency lockdown procedures) | B | Caretaker | 01/18/24 | Details |
01/10/24 | 115 | window covering recommended on 1st floor (emergency lockdown procedures) | B | Caretaker | 01/18/24 | Details |
01/10/24 | 111 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 120 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 101 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 202 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 122 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 127 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
01/10/24 | 113 | receptacle/light switch (specify) | A | Caretaker | 01/18/24 | Details |
02/28/24 | mechanical rooms | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 03/02/24 | Details |
02/28/24 | mechanical rooms | handrail not secure, damaged or required | A | Caretaker | 03/02/24 | Details |
02/28/24 | mechanical room 4 | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 03/02/24 | Details |
02/28/24 | 217 | ceiling tiles missing/loose | A | Caretaker | 03/02/24 | Details |
02/28/24 | mechanical room 2 | unable to inspect (specify why if possible) | B | Caretaker | 03/02/24 | Details |
02/28/24 | Washroom | unable to inspect (specify why if possible) | B | Caretaker | 03/02/24 | Details |
02/28/24 | 208 | window covering recommended on 1st floor (emergency lockdown procedures) | B | Principal | 02/28/24 | Details |
02/28/24 | 208 | lighting in need of repair (maintenance issue) | A | Caretaker | 03/02/24 | Details |
02/28/24 | 210 | lighting in need of repair (maintenance issue) | A | Caretaker | 03/02/24 | Details |
02/28/24 | 210T | lighting in need of repair (maintenance issue) | A | Caretaker | 03/02/24 | Details |
02/28/24 | 212-P | extinguisher - tag missing or annual inspection more than 3 months overdue | A | Caretaker | 03/02/24 | Details |
02/28/24 | 212-P | fire extinguisher not adequately charged or mounted | A | Caretaker | 03/02/24 | Details |
02/28/24 | Hallway | leaking/pooling/ponding of water or liquid (be as specific as possible) | A | Caretaker | 03/02/24 | Details |
02/28/24 | Hallway | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 03/02/24 | Details |
02/28/24 | Hallway | ceiling damaged (specify) | A | Caretaker | 03/02/24 | Details |
02/28/24 | Hallway | ceiling tiles missing/loose | A | Caretaker | 03/02/24 | Details |
03/01/24 | 217 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 215 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 213 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 211 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 209 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 207 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 205 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 201 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
03/01/24 | 219 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 03/07/24 | Details |
03/01/24 | 211 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Caretaker | | Details |
03/01/24 | 211 | eyewash station required or in need of repair (specify) | A | Caretaker | 03/07/24 | Details |
03/01/24 | M-4 ladder across Crtk. Off. | trip hazard (i.e. flooring, other materials) | A | Caretaker | 03/07/24 | Details |
03/01/24 | 219 | insufficient means of communication (ie: PA, radio, etc.) | B | | | Details |
03/01/24 | 201 | paint flaking, chipping, possible lead exposure | A | Caretaker | 03/07/24 | Details |
03/01/24 | 219 | display(s) not within TDSB standards as outlined by OH&S and Standards & Compliance (ie; artwork, hanging displays, paper on walls) | B | | | Details |
04/17/24 | Drama Room | multiport in use - potential fire hazard | B | | | Details |
04/17/24 | Drama Room | multiport in use - potential fire hazard | B | | | Details |
04/17/24 | Library | ceiling tiles missing/loose | A | Caretaker | 04/18/24 | Details |
04/17/24 | Gym A&B | ceiling damaged (specify) | A | Caretaker | 04/18/24 | Details |
05/31/24 | 102 | lighting in need of repair (maintenance issue) | A | Caretaker | 06/04/24 | Details |
05/31/24 | 127 | receptacle/light switch (specify) | A | Caretaker | 06/04/24 | Details |
05/31/24 | Boiler Room | exposed wiring/damaged cord/ground pin missing | A | Caretaker | 06/04/24 | Details |
05/31/24 | Hallway | ceiling damaged (specify) | A | Caretaker | 06/04/24 | Details |
05/31/24 | Hallway | lighting in need of repair (maintenance issue) | A | Caretaker | 06/04/24 | Details |
05/31/24 | 104 | lighting in need of repair (maintenance issue) | A | Caretaker | 06/04/24 | Details |
05/31/24 | 103 | window damaged, in need of repair (specify) | A | Caretaker | 06/04/24 | Details |
05/31/24 | 103 | window damaged, in need of repair (specify) | A | Caretaker | 06/04/24 | Details |
05/31/24 | 109 | lighting in need of repair (maintenance issue) | A | Caretaker | 06/04/24 | Details |
06/02/24 | 116 | ceiling tiles missing/loose | A | Caretaker | 06/10/24 | Details |
06/02/24 | 155 | door/access door (specify) | A | Caretaker | 06/10/24 | Details |
06/02/24 | Red Chair Lab | evidence of pests (interior or exterior), be as specific as possible. | A | Caretaker | 06/10/24 | Details |
06/02/24 | 213 | door/access door (specify) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 113 | lighting in need of repair (maintenance issue) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 117 | window covering damaged/in need of repair | A | Caretaker | 06/10/24 | Details |
06/02/24 | 127 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 129 | fire exit route sign (yellow TDSB) - not posted / requires updating | B | Caretaker | 07/19/24 | Details |
06/02/24 | 131 | HEPA Unit is not available per the TDSB HEPA guideline | B | | | Details |
06/02/24 | 126 | HEPA Unit is not available per the TDSB HEPA guideline | B | | | Details |
06/02/24 | 126 | damaged surface (ie: wall, ceiling, flashing, drywall, flooring, stairs) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 124 | window damaged, in need of repair (specify) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 116 | ceiling damaged (specify) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 120 | drain (specify) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 120 Storage | ceiling tiles missing/loose | A | Caretaker | 06/10/24 | Details |
06/02/24 | Vault - Main Office | evidence of pests (interior or exterior), be as specific as possible. | A | Caretaker | 06/10/24 | Details |
06/02/24 | 122 | trip hazard (i.e. flooring, other materials) | A | Caretaker | 06/10/24 | Details |
06/02/24 | Exit 6 | door/access door (specify) | A | Caretaker | 06/10/24 | Details |
06/02/24 | 122T | lighting in need of repair (maintenance issue) | A | Caretaker | 06/10/24 | Details |
06/02/24 | Staff Room | Workplace Inspection Form | B | | | Details |
06/02/24 | 114 | air - return/supply (specify) | A | Caretaker | 06/10/24 | Details |